REQUIREMENT |
VALUE |
REFERENCE STANDARD OR GUIDE
(including link) |
PROTECTION REQUIREMENTS |
|
|
Is an external accessible disconnecting switch mandatory? |
For plants with a performance less or equal 30 kVA is a facility for the monitoring of the grid with a particularly assigned switch in sequence necessary (ENS)
> 30 kVA: external accessible disconnecting switch mandatory |
DIN VDE 0100-551 (VDE 0100-551)
DIN VDE 0100-537 (VDE 0100-537)
DIN VDE 0126 (VDE 0126 )
Directives of the Association of the Energy and Water Industry |
What is the acceptable range of AC voltage for operation of DER? |
+/-10 % for Un = 230 V or 400 V
Undervoltage: 0,7 - 1,0 of rated voltage
Overvoltage: 1,0 - 1,15 of rated voltage |
DIN EN 50160 (April 2008)
DIN IEC 60038 (Standard Voltages)
DIN VDE 0100-551
IEC 60364-5-51 |
Is monitoring of voltage of each phase required? |
No |
|
What is the maximum allowed time for disconnection of DER in case of a voltage out of range event |
Voltage dip: 10 to 100 per year (10 ms up to 1 s, 1% up to 90% U n )
Short disconnection: 10 to 100 per year, 70% < 1 s (Duration: < 3 min)
Long disconnection: 10 to 50 per year (duration: > 3 min) |
|
What is the acceptable range of frequency for operation of DER |
Underfrequency: 47 - 50 Hz
Overfrequency: 50 - 52 Hz |
DIN EN 50160 (April 2008)
DIN VDE 0100-551
IEC 60364-5-51 |
What is the maximum allowed time for disconnection of DER in a case of a frequency out of range event |
|
|
What is the minimum time for reconnection after a disconnection of DER |
|
|
Other protection requirements |
|
|
IMPACT ON GRID-POWER QUALITY |
|
|
What is the allowable variation of voltage at LV side of LV/MV transformer, due to DER connection |
+- 10% |
DIN EN 50160 (April 2008) |
What is the limit of harmonic current emissions of DER |
According to regulations |
EN 61000-3-2
EN 61000-3-12 |
What is the limit of the voltage fluctuations and flicker for DER |
LV : According to regulations
MV: A lt : 0,1
P lt : 0,46 |
EN 61000-3-2
EN 61000-3-12 |
Requirements regarding power factor |
No compensation for DER up to 4.6 kVA in LV grids: 0.9 leading to 0.8 lagging is tolerated |
|
Other requirements for impact on grid-power quality |
|
|
PV SPECIFIC REQUIREMENTS |
|
|
Is an AC disconnecting switch mandatory for a PV plant |
YES |
DIN VDE 0126 (VDE 0126 ) |
What is the acceptable range for the settings of under-voltage disconnection |
|
|
What is the maximum allowed time for disconnection of a PV inverter in case of a voltage out of range event |
|
|
What is the acceptable range of settings for under- over frequency disconnection |
|
|
What is the maximum allowed time for disconnection of a PV inverter in case of a frequency out of range event |
200 ms |
DIN VDE 0126 (VDE 0126 ) |
What is the minimum time for reconnection after a disconnection of a PV inverter |
|
|
What is the limit of the total harmonic distortion of current of a PV inverter |
|
|
Is an isolation transformer required for a PV inverter |
|
|
What is the maximum allowable DC current injected to the grid |
|
|
Is any special protection required for transformerless inverters |
|
|
Is an anti-islanding protection for the PV inverter mandatory |
|
|
What method of anti-islanding protection is acceptable |
|
|